Therm 145 Deg C

Cable construction
  • Tinned Cu wires, according to IEC 60228 cl.5
  • Core insulation of polyolefin-copolymer
  • Flame test according to IEC 60332-3
  • Corrosiveness of combustion gases according to IEC 60754-2
  • Halogen free according to IEC 60754-1
  • Smoke density according to IEC 61034-1/61034-2
  • Good abrasion and notch resistance
  • Resistant to soldering temperatures
  • Lower propagation of fire
  • Resistant to UV radiation and ozone
Note

Please complete the part number for these cables by adding the suffix for the colour required as per list.
01= black, 02= gn-ye, 03= blue, 04= brown 05 = red, 06 = white, 07= grey, 08= vio, 09= dk-bu

Technical Data
  • Temperature range
    • Flexing: -35°C to +120°C
    • Fixed installation: -45°C to +145°C
  • Nominal voltage
    • Uo/u 300/500 V up to 1mm²
    • Uo/u 450/750 V from 1,5mm²
    • For fixed and protected installation
      Uo/u 600/1000V from 1,5mm²
  • Test voltage 3500V
  • Minimum bending radius
    • Flexing: 12,5 x cable Ø
    • Fixed installation: 4 x cable Ø
Application

These cables are mainly used for the internal wiring of electrical machinery, heaters, switching systems and lighting fixtures. Not approved for direct routing on racks, gutters or tanks. These cables are characterized by their amazingly long-time resistance to temperature and is among the leading halogen-free, flame resistant products.