Cable Screen LIYCY

Cable construction
  • Bare copper, fine wire conductors stranded to IEC 60228 cl 5
  • Special PVC core insulation T12
  • Colour coded to DIN 47100, but without colour repetition
  • Core wrapping with foil
  • Drain-wire, tinned
  • Tinned, copper braided screen, approx. 85% coverage
  • Special PVC outer sheath
  • Colour grey
  • Extensively oil resistant
  • PVC self-extinguishing and flame retardant according to IEC 60332-1
Technical Data
  • Temperature Range:
    • Flexing: -5°C to +80°C
    • Fixed installation: -40°C to +80°C
  • Nominal voltage: 0,14mm² = 350V > 0,25mm² =500V
  • Test voltage: core/core 1200 : core/screen 800V
  • Breakdown voltage: min. 2400V
  • Insulation resistance: min. 200 MOhm x km
  • Capacitance (approx. – value at 800 Hz)
    • core/core at 0,14mm² = 120 pF/m
    • core/core > 0,25mm² = 150 pF/m
    • core/screen at 0,14mm² = 240 pF/m
    • core/screen > 0,25mm² = 270 pF/m)
  • Inductance approx 0,65mH/km
  • Impedence approx 78 Ohm
  • Coupling resistance max. 250 Ohm/km
  • Minimum bending radius
    • Flexing: 10 x cable Ø
    • Fixed installation 5 x cable Ø
  • Radiation resistance up to 80 x 106 cJ/kg (up to 80 Mrad)
Application

This cables are used as junction or connecting cables in control, measuring and signaling technology as well as in data signalling technology as well as in data processing and office technology. Ideally suited for all types of connections on mobile equipment. The tight copper screening provides optimum protection against external electrical interference